Campbell-scientific CR3000 Micrologger Manual de usuario Pagina 536

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 590
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 535
Appendix B. Status Table and Settings
536
Table 124. Status-Table Fields and Descriptions
Fieldname Description Variable Type Default Range Edit? Info Type
MaxSlowProcTime9,13
The maximum time (s)
required to process
SlowSequence scan(s).
Integer array Status
PortStatus
Array of Boolean values
posting the state of control
ports. Values updated every
500 ms.
Boolean array of 8 False True or False Yes Status
PortConfig
Array of strings explaining
the use of the associated
control port. Valid entries
are: Input, Output, SDM,
SDI-12, Tx, and Rx.
String array of 8 Input Input or Output Status
SW12Volts
Status of switched, 12-Vdc
port
Boolean False True or False Yes Status
Security14
Array of the three security
settings or codes. Will not be
shown if security is enabled.
Integer array of 3 0, 0, 0
0 - 65535 (0 is
no security)
Yes Status
RS232Power
Controls whether the RS-232
port will remain active even
when communication is not
taking place. If RS-232
handshaking is enabled
(handshaking buffer size is
non-zero), this setting must
be set to yes
Boolean 0 0 or 1
RS232Handshaking
RS-232 hardware-
handshaking buffer size. If
non-zero, hardware
handshaking is active on the
RS-232 port. This setting
specifies the maximum
packet size sent between
checking for CTS.
Integer 0
RS232Timeout
RS-232 hardware-
handshaking timeout. For
RS-232 hardware
handshaking, this specifies in
tens of ms the timeout that
the datalogger will wait
between packets if CTS is
not asserted.
Integer 0
Vista de pagina 535
1 2 ... 531 532 533 534 535 536 537 538 539 540 541 ... 589 590

Comentarios a estos manuales

Sin comentarios