Appendix B. Status Table and Settings
511
Table 117. Status-Table Fields and Descriptions
Fieldname Description Variable Type Default Range Edit? Info Type
ProcessTime
Processing time (μs) of the
last scan. Time is measured
from the end of the EndScan
instruction (after the
measurement event is set) to
the beginning of the EndScan
(before the wait for the
measurement event begins)
for the subsequent scan.
Calculated dynamically (on
the fly).
Integer Status
MaxProcTime
Maximum time (μs) required
to run through processing for
the current scan. This value
is reset when the scan exits.
Calculated dynamically (on
the fly).
Integer
Yes
Reset by
changing to 0
Status
BuffDepth
Shows the current Pipeline
Mode processing buffer
depth., which indicates how
far processing is currently
behind measurement.
MaxBuffDepth
Gives the maximum number
of buffers processing lagged
measurement.
LastSystemScan8
The last time the background
calibration executed.
Integer array Status
LastSlowScan9
The last time SlowSequence
scan(s) executed.
Integer array Status
SystemProcTime8,12
The time (μs) required to
process the background
calibration.
Integer array Status
SlowProcTime9,12
The time (μs) required to
process SlowSequence
scan(s).
Integer array Status
MaxSystemProcTime8,
13
The maximum time (μs)
required to process the
background calibration.
Integer array Status
MaxSlowProcTime9,13
The maximum time (μs)
required to process
SlowSequence scan(s).
Integer array Status
PortStatus
Array of Boolean values
posting the state of control
ports. Values updated every
500 ms.
Boolean array of 8 False True or False Yes Status
PortConfig
Array of strings explaining
the use of the associated
control port. Valid entries
are: Input, Output, SDM,
SDI-12, Tx, and Rx.
String array of 8 Input Input or Output Status
SW12Volts
Status of switched, 12-Vdc
port
Boolean False True or False Yes Status