MET ONE 034A-L WINDSET
5
07: Real Time (P77)
1: 0110 Day,Hour/Minute
08: Wind Vector (P69)
1: 1 Reps
2: 0 Samples per Sub-Interval
3: 00 S, θu, & σ(θu) Polar**
4: 1* Wind Speed [ WndS_m_s ]
5: 2* Wind Direction [ WndD_deg ]
-Input Locations-
1 WndS_m_s
2 WndD_deg
EXAMPLE 2. Sample 21X Instructions
;{21X}
;
*Table 1 Program
01: 10 Execution Interval (seconds)
01: Pulse (P3)
1: 1 Reps
2: 2* Pulse Channel 2
3: 22 Switch Closure, Output Hz
4: 1* Loc [ WndS_m_s ]
5: 0.7990 Mult
6: 0.2811 Offset
;Set the wind speed to zero if the wind is not blowing.
;
02: If (X<=>F) (P89)
1: 1* X Loc [ WndS_m_s ]
2: 1 =
3: 0.2811 F
4: 30 Then Do
03: Z=F (P30)
1: 0 F
2: 1* Z Loc [ WndS_m_s ]
04: End (P95)
05: AC Half Bridge (P5)
1: 1 Reps
2: 5 ± 5000 mV Slow Range
3: 5* SE Channel
4: 3* Excite all reps w/Exchan 3
5: 5000 mV Excitation
6: 2* Loc [ WndD_deg ]
7: 720 Mult
8: 0 Offset
06: If time is (P92)
1: 0 Minutes (Seconds --) into a
2: 30 Interval (same units as above)
3: 10 Set Output Flag High (Flag 0)
Comentarios a estos manuales