CS105/CS105MDBarometric Pressure SensorRevision: 3/07Copyright © 1995-2007Campbell Scientific, Inc.
CS105/CS105MD Barometric Pressure Sensor 4. Programming 4.1 CS105MD Programming the MetData1 station for the CS105MD is done through Campbell Scient
CS105/CS105MD Barometric Pressure Sensor Example 1. CR1000 Program for Measuring the CS105 Once Every Hour 'Main Program BeginProg Scan(5,Sec,1
CS105/CS105MD Barometric Pressure Sensor 07: Real Time (P77) 1: 0110 Day,Hour/Minute 08: Sample (P70) 1: 1 Reps 2: 1* Loc [ P_mb ]
CS105/CS105MD Barometric Pressure Sensor -Input Locations- 1 P_mb * Proper entries will vary with program and datalogger channel, and input locatio
CS105/CS105MD Barometric Pressure Sensor Example 5. CR10(X) Program for Measuring the CS105 Once Every Hour with Instruction 2 (Differential Measurem
CS105/CS105MD Barometric Pressure Sensor 6. Correcting Pressure to Sea Level The weather service, most airports, radio stations, and television stati
CS105/CS105MD Barometric Pressure Sensor This is a blank page. 12
Appendix A. Daily Average If the CS105 will be measured every minute or faster, and a daily average is required, follow Example 5. In Example 5 the
Appendix A. Daily Average 08: Average (P71) 1: 1 Reps 2: 2* Loc [ P_const ] 09: If Flag/Port (P91) 1: 10 Do if Output Flag is Hig
This is a blank page.
Warranty and Assistance The CS105/CS105MD BAROMETRIC PRESSURE SENSOR is warranted by CAMPBELL SCIENTIFIC, INC. to be free from defects in materials an
Campbell Scientific Companies Campbell Scientific, Inc. (CSI) 815 West 1800 North Logan, Utah 84321 UNITED STATES www.campbellsci.com info@campbells
CS105/CS105MD Table of Contents PDF viewers note: These page numbers refer to the printed version of this document. Use the Adobe Acrobat® bookmarks
This is a blank page.
CS105/CS105MD Barometric Pressure Sensor 1. General The CS105 analog barometer uses Vaisala’s Barocap® silicon capacitive pressure sensor. The Baroc
CS105/CS105MD Barometric Pressure Sensor Supply Voltage: 10 to 30 VDC Supply Voltage Control: When enabled with an internal jumper, the CS105 is on
CS105/CS105MD Barometric Pressure Sensor FIGURE 1. CS105 Mounted on the Backplate of an ENC12/14 Enclosure, and Connected to a CR1000 Datalogger INT
CS105/CS105MD Barometric Pressure Sensor VAISALAEXT. TRIGAGNDGNDSUPPLYVOUTPRESSURE TRANSMITTERMODELSERIAL NORANGEOUTPUTSUPPLYPTB101BP4450003600-1060 h
CS105/CS105MD Barometric Pressure Sensor VAISALAEXT. TRIGAGNDGNDSUPPLYVOUTPRESSURE TRANSMITTERMODELSERIAL NORANGEOUTPUTSUPPLYPTB101BP4450003600-1060 h