WindSonic Two-Dimensional Sonic Anemometer
*Table 3 Subroutines
End Program
-Input Locations-
1 wnd_dir
2 wnd_spd
3 ws_diag
4 samples
7.4.2 Example CR200(X) Datalogger Program for Measuring a
WindSonic4
TABLE 7-11. Wiring for CR200(X) Program Example
Description Color CR200(X)
SDI-12 data Green C1/SDI-12
SDI-12 power Red +12 Vdc
SDI-12 reference Black G
Shield Clear G
'CR200(X) Series Datalogger
Public windsonic(3)
Alias windsonic(1) = wind_direction
Alias windsonic(2) = wind_speed
Alias windsonic(3) = diag
Units wind_direction = degrees
Units wind_speed = m/s
Units diag = unitless
Dim disable_flag
Dim one
Units one = samples
DataTable (stats,TRUE,-1)
DataInterval (0,30,Min)
WindVector (wind_speed,wind_direction,disable_flag,0,0)
FieldNames ("mean_wnd_spd,mean_wnd_dir,std_wnd_dir")
Totalize (1,one,disable_flag)
FieldNames ("n_TOT")
Totalize (1,one,diag<>1)
FieldNames ("diag_1_TOT")
Totalize (1,one,diag<>2)
FieldNames ("diag_2_TOT")
Totalize (1,one,diag<>4)
FieldNames ("diag_4_TOT")
Totalize (1,one,diag<>8)
FieldNames ("diag_8_TOT")
Totalize (1,one,diag<>9)
FieldNames ("diag_9_TOT")
Totalize (1,one,diag<>10)
FieldNames ("diag_10_TOT")