APPENDIX B. CONTROL PORT SERIAL I/O INSTRUCTION 15
B-15
11: 1 Multiplier
12: 0 Offset
06: P End Table 1
Input Location Labels:
1:VALUE #1 4:VALUE #4 7:VALUE #7 10:VALUE #10
2:VALUE #2 5:VALUE #5 8:VALUE #8 11:COUNTER
3:VALUE #3 6:VALUE #6 9:VALUE #9 12:_________
CR10X#2 PROGRAM - RECEIVE DATA
* 3 Table 3 Subroutines
01: P85 Beginning of Subroutine
01: 98 Subroutine Number
02: P15 Control Port Serial I/O
01: 1 Repetitions
02: 1 Configuration code RS-232, 1200 bd
03: 0 CTS/Delay before send
04: 6 C6 RTS/DTR RXD = C7 (code could be 76)
05: 0 Output start location
06: 0 Number of locations to send
07: 13 Input termination character Terminate on carriage return
08: 75 Max characters to receive
09: 200 Delay for CTS/input Wait 2 seconds for input
10: 11 First input location Store VALUE #1 in Location 11, #10 in 20
11: 1 Multiplier
12: 0.0000 Offset
03: P95 End
Input Location Labels:
11:VALUE #1 16:VALUE #6
12:VALUE #2 17:VALUE #7
13:VALUE #3 18:VALUE #8
14:VALUE #4 19:VALUE #9
15:VALUE #5 20:VALUE #10