Campbell-scientific SDM-AO4A Four Channel Analog Output Module Manual de usuario Pagina 5

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 20
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 4
SDM-AO4A Four Channel Analog
Output
1. Function
The SDM-AO4A is designed to output four continuous voltages at levels set
by a Campbell Scientific datalogger.
The SDM-AO4A is a replacement for the SDM-AO4. However, the SDM-
AO4A offers several new features including a 0-10 V Mode, a choice of
synchronous or sequential operation, and SDM signature checking. In
addition, the SDM-AO4A has higher resolution, improved accuracy, and high
drive current for sensor excitation.
2. Specifications
± 5 V mode 10 V mode
Vsupply
12 V Nominal (9.6 to 16 V)
Iq (no load, Vout = 0, Vsupply = 12 V)
11 mA typical 21 mA typical
Iq (no load, Vout = Fullscale, Vsupply = 12 V)
13 mA typical 28 mA typical
Iq (w/ load, Vsupply = 12 V)
13 mA + load typical 28 mA + 2.4*load typical
Iq (power down mode, Vsupply = 12 V)
1.1 mA typical
Range
± 5 V 0-10 V
Resolution
167 µV
Accuracy @ 25°C (20 kOhm load)
± (0.05% of |Vout(V)| + 500 µV) max
Accuracy @ -40° to 60°C (20 kOhm load)
± (0.1% of |Vout(V)| + 500 µV) max
Additional Fullscale Error w/ 50 mA load
-1.3 mV typical -1.5 mV typical
Max Iout per Channel
50 mA
Max Iout Total
100 mA
Overcurrent shutdown point
130 ± 15 mA
Size
5.3" x 3.35" x 0.95" (13.46 x 8.51 x 2.41 cm)
Weight
6.2 oz (175 grams)
Operating Temperature Range
-40° to +60°C