CS451/CS456 Submersible Pressure Transducer
FIGURE 8-2. Connect screen
There are three settings that can be changed: SDI-12 address, Pressure/Level
Units, and Temperature Units. Double-click on the window of the units to be
changed. This will open a pick menu box. Select the desired units and Apply
the changes.
8.2 SDI-12 Commands
This section briefly describes using the SDI-12 commands.
Additional SDI-12 information is available at Appendix D,
SDI-12 Sensor Support, www.sdi-12.org, or
www.youtube.com/user/CampbellScientific
.
The CS451/CS456 uses an SDI-12 compatible hardware interface and supports
a subset of the SDI-12 commands. The most commonly used command is the
aM! command, issued by the datalogger, where a represents the sensor
address. The communication sequence begins with the datalogger waking the
sensor and issuing the aM! command. The transducer responds to the
datalogger indicating that two measurements will be ready within two seconds.
Subsequent communications handle data reporting from the sensor to the
datalogger.
The SDI-12 protocol has the ability to support various measurement
commands. The CS451/CS456 supports the commands that are listed in
TABLE 8-3.
NOTE
16